Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

05/31/2006

Applicant:

SMITH MARCELINE C

Description:

numerous fire code violations in commercial kitchen.

Outstanding Inspections

Case Number: T06FR01634
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
05/31/2006 INSP - FULL RDUARTE Correction Required Shooters Steak House & Saloon with numerous fire code violations in commercial kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR01634
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 10
End Date Description Inspector Results Comments
02/06/2002 VIOL - FIRE RESIST.RATED CONST DRAMIREZ Approved TFC 703.1 Opening in the ceiling over the exterior door in kitchen area shall be protected from passage of smoke or fire.
02/06/2002 VIOL - COMPRESSED GASES DRAMIREZ Approved TFC 3003.5 Secure compressed gas cylinders. 1.) behind bar, south end corner. 2.) outside area, next to coolers.
02/06/2002 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1011.1 Provide exit sign over exterior door in the billiards room area.
02/06/2002 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1006.3 Emergency back-up lightung shall be provided. 1.) main bar area. 2.) main dining room area. 3.) billards room area.
06/02/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 904.11 Current hood system is not in compliance. Shall comply in accordance to following codes: 1.) 609.1 ( Requirments of the International Mechanical Code) 2.) 609.2 ( Type of hood system required) 3.) 904.11 ( Installation and testing)
06/02/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 906.7 Portable extinguishers shall be on hangers and accesseble.
06/02/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 308.3.1 Open flame cooking devices shall not be operated within 10 feet of combustible construction.
06/02/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.5 Extension cords shall not be a subsitute for permanent wiring. 1.) outside office, running through ceiling. 2.) over exit door, kitchen area. 3.) outside cooler area.
06/02/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.3 Shall maintain a clear and working space around electrical panel.
06/02/2006 COMPL - INITIAL INSPECTION DRAMIREZ Approved 1.) Pre-citation issued. Non-compliant hood system. Was given one week to present documentation indicating that permit was issued showing intent to upgrade or replace hood system. 2.) Deep fryer appliances RED TAGGED. Required seperation between open flame and fryers. 3.) Initiated full inspection.