Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/19/2006

Applicant:

LANGFAN WILLIAM K TR

Description:

Fire Inspection

Outstanding Inspections

Case Number: T06FR01406
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
05/19/2006 VIOL - FIRE SERVICE FEATURES KFOSTER Correction Required TFC-505.1 Address Numbers. 1) Address the building according to the Pima County Address Display Requirements left.
05/19/2006 VIOL - BUILDING SVCS & SYSTEMS KFOSTER Correction Required TFC- 605.1 Electrical Hazards. 4) Remove white exstion cord running over south exit door.
05/19/2006 VIOL - MEANS OF EGRESS KFOSTER Correction Required TFC- 1003.6 Means of Egress. 3) Unblock south exit, maintain a clear path to exit.
05/19/2006 VIOL - COMPRESSED GASES KFOSTER Correction Required TFC- 3003.3.3 Compressed Gas Cylinders. 2) Chain compressed gas cylinders to prevent being knocked over, east wall.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR01406
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/16/2007 INSP - FULL JBURGE Approved The following Tucson Fire Code violations were corrected during the second re-inspection. Inspector John Bieg 1-16-07. Case closed.