05/17/2006

Applicant:

CACTUS HARDWARE INC

Description:

full inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR01396
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
05/17/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 315.2.1 Sprinkler head in storage room shall be free from obsrtuction . You shall provide at least 18 inches of clearance below sprinkler head .
05/17/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 906.5 Portable fire extinguisherby main enterance shall be located in conspicuous location and readily accessible for immediate use .
05/17/2006 INSP - FULL DRAMIREZ Approved