Case: T06FR01334
Case Details
Entered Date:
05/12/2006
Applicant:
HARTING STEVEN A TR
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR01334
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2006 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 Storage shall not be in electrical equipment room. |
| 05/12/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Blank needed at panel in equipment room. |
| 05/12/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Outlet at east wall of equipment room. |
| 05/12/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Extinguisher at east wall of west building. outside |
| 05/12/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 extinguisher between ice machines. |
| 05/12/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.1 Grease filter at fryer |
| 05/12/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 West kitchen exit. |
| 05/12/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.4 Surface locks on dining area doors. |
| 05/12/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign at the east exit |
| 05/12/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 East exits obstructed |
| 05/12/2006 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 Cylinders at drive thru |
| 05/12/2006 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 Cylinders at equipment room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR01334
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2009 | INSP - FULL | TKNAPP | Approved |