Case: T06FR01200
Case Details
Entered Date:
05/05/2006
Applicant:
CAMELBACK CORP CENTER JOINT VENTURE LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR01200
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2006 | INSP - FULL | NSPRENGE | Violation | |
| 03/29/2006 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | 1. IFC 2003 305.1 Clearance between ignition sources and combustible materials shall be maintained in an approved manner. |
| 03/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 1. IFC 2003 605.4 Multi plug adapters are prohibited and shall not be used. Remove multiplug adapters form 1st cubicles on N and S sides , 2nd cubicle, 4th cubicle on S side, and in the back storage room connected to tv. |
| 04/05/2006 | INSP - REINSPECTION | NSPRENGE | Continued | Still have some adapters in use. Gave 1 more week for compliance. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR01200
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2006 | COMPL - REINSPECTION | NSPRENGE | Approved | Approved. |
| 05/05/2006 | COMPL - REINSPECTION | NSPRENGE | Approved | Multiplug adapters have been removed and replaced with power strips with circuit breakers. Clearance maitained around hot water heater. |