Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/05/2006

Applicant:

CAMELBACK CORP CENTER JOINT VENTURE LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T06FR01200
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
03/29/2006 INSP - FULL NSPRENGE Violation
03/29/2006 VIOL - PRECAUTION AGAINST FIRE NSPRENGE Violation 1. IFC 2003 305.1 Clearance between ignition sources and combustible materials shall be maintained in an approved manner.
03/29/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 1. IFC 2003 605.4 Multi plug adapters are prohibited and shall not be used. Remove multiplug adapters form 1st cubicles on N and S sides , 2nd cubicle, 4th cubicle on S side, and in the back storage room connected to tv.
04/05/2006 INSP - REINSPECTION NSPRENGE Continued Still have some adapters in use. Gave 1 more week for compliance.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR01200
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/05/2006 COMPL - REINSPECTION NSPRENGE Approved Approved.
05/05/2006 COMPL - REINSPECTION NSPRENGE Approved Multiplug adapters have been removed and replaced with power strips with circuit breakers. Clearance maitained around hot water heater.