Description:

gates don't work properly in this gated community, manual overide does not work for any car to go out or come in. concern about evacuating incase of a fire.

Outstanding Inspections

Case Number: T06FR01034
Case Status: FIELD
Case Description: COMPLAINT (RESIDENTIAL)
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
04/27/2006 INSP - FULL RSUMMER Correction Required jvalenz1 assigned.
05/23/2006 VIOL - FIRE SERVICE FEATURES JVALENZU Violation 1. TFC 503.6 Security gates - Where security gates are installed, they shall have an approved means of emergency operation. The security gates and emergency operation shall be maintained operational at all times.
05/23/2006 VIOL - FIRE SERVICE FEATURES JVALENZU Violation 2. TFC 503.6.1 Electric opening gates - Gates that use electric or other means of power to automatically open or unlock shall have a manual override system. Manual controls shall be located on the entrance side of gate, or when power has failed, the gate(s) shall open and stay open until the power is restored for normal operations
05/23/2006 VIOL - FIRE SERVICE FEATURES JVALENZU Violation 3. TFC 503.6.2 Fire apparatus access road gates - Gates/barricades securing the fire apparatus roads shall comply with all of the following criteria: 1. The minimum gate width shall be 20 feet unobstructed. 2. Gates shall be of the swinging or sliding type. 3. Construction of gates shall be of materials that allow manual operation by one person. 4. Gate components shall be maintained in an operative condition at all times and replaced or repaired when defective. 5. Electric gates shall be equipped with a means of opening the gate by fire department personnel for emergency access on to the property or leaving the property. 6. Locking device specifications shall be submitted for approval by the fire code official. 7. Gates/barricades that are permanently secured for access reasons shall be posted with the approved fire access signs, on both sides of the gate/barricade. Signs can be mounted on gate or follow requirements under section Appendix D.