Case: T06FR01016
Case Details
Entered Date:
04/26/2006
Applicant:
MARBRY ENTERPRISES LLC
Description:
operations fire inspections, check list used.
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR01016
Case Description: INSPECTION
Total Completed Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2006 | VIOL - COMPRESSED GASES | SHIGGINB | Approved | 36.TFC 3004.1 O2 storage and Use Can be on a 45 degree, Must be secured w/ straps or rack No smoking signs must be posted on front door |
| 05/01/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 29. TFC 1027.2 Must be able to use easily and reliable Check if they open and look at security devices |
| 05/01/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 26.TFC 1008.18 Door operation No double key dead-bolt locks, no special knowledge needed, no slide bolt locks. Only one unlatching device, Except group R’s can have night latch, indicating dead bolt, or security chain on exits only |
| 05/01/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | 21.TFC 605.4 Multi-plugs and power-taps UL listed,No end to end, home made |
| 05/01/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | 20. TFC 605.5 Extension cords Grounds, used as permanent wiring, run under carpet, attached to walls can be replaced w/ power strip that has overcurrent protection |
| 05/01/2006 | VIOL - EMERGENCY PLAN/PREPARE | SHIGGINB | Approved | 15. TFC 901.6.2 Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. |
| 05/01/2006 | VIOL - EMERGENCY PLAN/PREPARE | SHIGGINB | Approved | 14. TFC 405.5 Fire drill documentation on site Included training for staff and drills for residents. Should have date, staff names, and times to evacuate. |
| 05/01/2006 | INSP - FULL | SHIGGINB | Approved | ASL LIC FOR 10 |