Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/19/2006

Applicant:

T C REAL ESTATE LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T06FR00823
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
03/29/2006 INSP - FULL NSPRENGE Correction Required
03/29/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.1 ELECTRICAL HAZARDS SHALL BE EBATED. INSTALL BLANKS IN UPSTAIRS ELECTRICAL PANEL WHERE BREAKERS ARE MISSING AND SECURE PANEL TO BOX.
03/29/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.6 OPEN JUNCTION BOXES SHALL BE PROHIBITED. INSTALL COVER ON JUNCTION BOX.
03/29/2006 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Violation IFC 2003 - 901.6 FIRE EXTINGUISHERS MUST BE INSPECTED ANNUALLY. UPSTAIRS EXTINGUISHER NEEDS TO BE INSPECTED.
03/29/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 2003 - 1008.1.8.4 SLIDE BOLTS ARE NOT PERMITTED ON EXITS. REMOVE SLIDE BOLT FROM REAR EXIT.
03/29/2006 VIOL - COMPRESSED GASES NSPRENGE Violation IFC 2003 3003.3 COMPRESSED GAS CONTAINERS SHALL BE SECURED AGAINST ACCIDENTAL DISLODGEMENT. SECURE TANKS IN PLACE.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR00823
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/12/2006 COMPL - REINSPECTION NSPRENGE Approved All violations corrected and compliance met.