Case Details

Status:

REFERRED

Type:

INSPECTION
Address:

Entered Date:

04/07/2006

Applicant:

LAKE INVESTMENT GROUP LLC

Description:

inspection

Completed Inspections

Case Status: REFERRED
Case Number: T06FR00698
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
04/07/2006 INSP - FULL EGRIFFIN Approved 1). Certificate of Occupancy shall be posted recognizing current use of the building. 2). Fire alarm test report shall be submitted to TFD and all required repairs shall be completed. IFC 901.6 3). Currently smoke detector in 2 years old room has no battery back up and in 3 year old room no smoke detectors exist. Proper smoke detectors shall be installed. IFC 907.3.2 4). Monthly checks of portable fire extinguishers are required. Info given. IFC 901.6
05/08/2006 COMPLIANCE EGRIFFIN Approved C of O still pending