Case: T06FR00544
Case Details
Entered Date:
03/30/2006
Applicant:
BUSINESS PARK
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T06FR00544
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
03/17/2006 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 2003 605.3 ELECTRICAL PANEL WORKING SPACE SHALL BE 36 " CLEAR IN WIDTH. REMOVE OVERSTOCK BLOCKING ELECTRICAL PANEL. |
03/17/2006 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 2003 605.4 MULTIPLUG ADAPTERS PROHIBITED REMOVE MULTIPLUG ADAPTER FROM L FRONT COUNTER |
03/17/2006 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 2003 605.5 GENERAL EXT CORDS; REMOVE EXT CORD FROM L FRONT COUNTER AND R FRONT WINDOW |
04/06/2006 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | IFC 2003 315.2 COMBUSTIBLE STORAGE SHALL BE ORDERLY. ORGANIZE BOXES IN STOCK AREA SO AS TO ALLOW 36 " AISLE WIDTH AND BREAK UP FUEL LOAD. |
04/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | IFC 2003 901.4 SPRINKLER RISER SHALL BE ACCESSIBLE. MAINTAIN 4 ' CLEARANCE AROUND SPRINKLER RISER. |
04/06/2006 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 2003 1016.2 MAINTAIN 36 " AISLE WIDTH IN STOCK AREAS. |
04/06/2006 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 2003 1027.2 REQUIRED EXIT ACCESSES AND DISCHARGES SHALL BE FREE FROM OBSTRUCTIONS. REMOVE BOXES AND OVERSTOCK BLOCKING WEST EXIT DOOR. |
04/06/2006 | VIOL - HAZARDOUS MATERIALS,GEN | NSPRENGE | Violation | IFC 2003 2703.4 MATERIAL SAFETY DATA SHEETS SHALL BE READILY AVAILABLE ON THE PREMISES FOR HAZARDOUS MATERIALS REGULATED BY THIS CHAPTER. ACQUIRE MSDS FOR YOUR HAZARDOUS MATERIALS. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR00544
Case Description: INSPECTION
Total Completed Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2006 | INSP - REINSPECTION | NSPRENGE | Approved | IFC 2003 - 605.3 - 36 " CLEARANCE PROVIDED AROUND ELECTRICAL PANEL. |
04/05/2006 | INSP - REINSPECTION | NSPRENGE | Approved | IFC 901.4 THERE IS 4 ' CLEARANCE AROUND SPRINKLERS. |
04/05/2006 | INSP - REINSPECTION | NSPRENGE | Approved | IFC 1027.2 EXITS CLEAR OF BOXES AND OVERSTOCK. HAZARD ABATED. |
04/05/2006 | INSP - REINSPECTION | NSPRENGE | Approved | IFC 605.4 MULTIPLUG ADAPTERS HAVE BEEN REMOVED. HAZARD ABATED. |
04/05/2006 | INSP - REINSPECTION | NSPRENGE | Approved | IFC 605.5 EXTENSION CORDS HAVE BEEN REMOVED. HAZARD ABATED. |
04/13/2006 | COMPL - REINSPECTION | NSPRENGE | Approved | ALL LISTED HAZARDS ABATED AND BUILDING BUSINESS IN COMPLIANCE. |
04/13/2006 | COMPL - REINSPECTION | NSPRENGE | Approved | IFC 1016.2 - THERE IS 36 " WIDTH SPANNING ENTIRE REAR STOCK ROOM. HAZARDS ABATED. |
04/13/2006 | COMPL - REINSPECTION | NSPRENGE | Approved | IFC 315.2 COMBUSTIBLE STORAGE IS ORDERLY |
04/13/2006 | COMPL - REINSPECTION | NSPRENGE | Approved | IFC 2703.4 MSDS HAVE BEEN ACQUIRED FOR CHEMICALS ON SHELF AND IN STOCK. |