Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/30/2006

Applicant:

BUSINESS PARK

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T06FR00544
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
03/17/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.3 ELECTRICAL PANEL WORKING SPACE SHALL BE 36 " CLEAR IN WIDTH. REMOVE OVERSTOCK BLOCKING ELECTRICAL PANEL.
03/17/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.4 MULTIPLUG ADAPTERS PROHIBITED REMOVE MULTIPLUG ADAPTER FROM L FRONT COUNTER
03/17/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.5 GENERAL EXT CORDS; REMOVE EXT CORD FROM L FRONT COUNTER AND R FRONT WINDOW
04/06/2006 VIOL - PRECAUTION AGAINST FIRE NSPRENGE Violation IFC 2003 315.2 COMBUSTIBLE STORAGE SHALL BE ORDERLY. ORGANIZE BOXES IN STOCK AREA SO AS TO ALLOW 36 " AISLE WIDTH AND BREAK UP FUEL LOAD.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Violation IFC 2003 901.4 SPRINKLER RISER SHALL BE ACCESSIBLE. MAINTAIN 4 ' CLEARANCE AROUND SPRINKLER RISER.
04/06/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 2003 1016.2 MAINTAIN 36 " AISLE WIDTH IN STOCK AREAS.
04/06/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 2003 1027.2 REQUIRED EXIT ACCESSES AND DISCHARGES SHALL BE FREE FROM OBSTRUCTIONS. REMOVE BOXES AND OVERSTOCK BLOCKING WEST EXIT DOOR.
04/06/2006 VIOL - HAZARDOUS MATERIALS,GEN NSPRENGE Violation IFC 2003 2703.4 MATERIAL SAFETY DATA SHEETS SHALL BE READILY AVAILABLE ON THE PREMISES FOR HAZARDOUS MATERIALS REGULATED BY THIS CHAPTER. ACQUIRE MSDS FOR YOUR HAZARDOUS MATERIALS.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR00544
Case Description: INSPECTION
Total Completed Inspections - 9
End Date Description Inspector Results Comments
04/05/2006 INSP - REINSPECTION NSPRENGE Approved IFC 2003 - 605.3 - 36 " CLEARANCE PROVIDED AROUND ELECTRICAL PANEL.
04/05/2006 INSP - REINSPECTION NSPRENGE Approved IFC 901.4 THERE IS 4 ' CLEARANCE AROUND SPRINKLERS.
04/05/2006 INSP - REINSPECTION NSPRENGE Approved IFC 1027.2 EXITS CLEAR OF BOXES AND OVERSTOCK. HAZARD ABATED.
04/05/2006 INSP - REINSPECTION NSPRENGE Approved IFC 605.4 MULTIPLUG ADAPTERS HAVE BEEN REMOVED. HAZARD ABATED.
04/05/2006 INSP - REINSPECTION NSPRENGE Approved IFC 605.5 EXTENSION CORDS HAVE BEEN REMOVED. HAZARD ABATED.
04/13/2006 COMPL - REINSPECTION NSPRENGE Approved ALL LISTED HAZARDS ABATED AND BUILDING BUSINESS IN COMPLIANCE.
04/13/2006 COMPL - REINSPECTION NSPRENGE Approved IFC 1016.2 - THERE IS 36 " WIDTH SPANNING ENTIRE REAR STOCK ROOM. HAZARDS ABATED.
04/13/2006 COMPL - REINSPECTION NSPRENGE Approved IFC 315.2 COMBUSTIBLE STORAGE IS ORDERLY
04/13/2006 COMPL - REINSPECTION NSPRENGE Approved IFC 2703.4 MSDS HAVE BEEN ACQUIRED FOR CHEMICALS ON SHELF AND IN STOCK.