Case Number: T06FR00442
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 03/21/2006 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy. |
| 03/21/2006 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Combustible storage shall be maintained 18" below sprinkler head deflectors. 1. office 2. storage areas 3. locker room |
| 03/21/2006 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.3- Combustible materials shall not be stored in electrical rooms. (outside) |
| 03/21/2006 | VIOL - FIRE SERVICE FEATURES | JLANGEJA | Violation | TFC 505.1- Address numbers shall be in accordance with Pima County address display requirements. See handout. |
| 03/21/2006 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Electrical hazards shall be abated. 1. electrical cord through ceiling 2. electrical box under sink 3. flex tubing on oven 4. exposed wires outside freezer 5. electrical receptacle outside shall be protected (NW corner) |
| 03/21/2006 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters shall not be permitted. 1. mechanical room on south wall |
| 03/21/2006 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes shall be prohibited. 1. bus station in dining area (East wall) |
| 03/21/2006 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Fire resistive-rated construction shall be maintained. 1. ceiling tiles in office (x 2) 2. ceiling tile in mechanical room |
| 03/21/2006 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1004.3- Assembly occupancies shall have the occupant load posted in a conspicuous place near the main exit. |
| 03/21/2006 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1006.3- In the event of a power failure, an emergency electrical system shall automatically illuminate the following: 1. exit access corridors 2. passageways and aisles in rooms that require 2 exits |
| 03/21/2006 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.2- Exit signs shall be internally or externally illuminated at all times. (several throughout, check all) |
| 03/21/2006 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.5.3- In case of primary power loss, exit signs shall continue illumination for a duration of not less than 90 minutes. (several throughout, check all) |
| 03/21/2006 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured against accidental dislodgement. (x 6) |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR00442
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2006 | INSP - REINSPECTION | JLANGEJA | Approved | All violations have been corrected. |