Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

03/14/2006

Applicant:

ROATH PROPERTIES LLC

Description:

inspection

Outstanding Inspections

Case Number: T06FR00362
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 19
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
03/14/2006 VIOL - ADMINISTRATION JVALENZU Violation · TFC 102.6 - Building code Certificate of Occupancy - no building or structure shall be used or occupied until the building official has issued a certificate of occupancy. A C of O shall be mounted in a conspicuous place.
03/14/2006 VIOL - PRECAUTION AGAINST FIRE JVALENZU Violation · TFC 304.1 - combustible waste material shall not be allowed to accumulate in buildings or upon premises. Remove the wood that is stored between the buildings.
03/14/2006 VIOL - BUILDING SVCS & SYSTEMS JVALENZU Violation · TFC 605.3 - a working space of not less than 30"Wx36"Dx78"H shall be provided in front of electrical service equipment. This applies to all breaker panels and service disconnects inside and outside the building.
03/14/2006 VIOL - BUILDING SVCS & SYSTEMS JVALENZU Violation · TFC 605.4 - multiplug adapters shall be prohibited. There are several throughout the building. A fused plug strip is approved when plugged directly into a permanent wall receptacle.
03/14/2006 VIOL - BUILDING SVCS & SYSTEMS JVALENZU Violation · TFC 605.5 - extension cords shall not be used as a substitute for permanent wiring, shall not be affixed to structures, extend through walls, ceilings or floors or under doors or floor coverings. Currently there are numerous extension cords throughout the entire building and outside on the porches.
03/14/2006 VIOL - BUILDING SVCS & SYSTEMS JVALENZU Violation · TFC 605.6 - open junction boxes and open-wiring splices shall be prohibited. Currently there is a junction box and light fixture that needs a cover in the kitchen area, a box in the ceiling of the VIP room, the breaker panel on the back porch needs a cover, the timer box on the back porch needs a cover, splices in wires at the breaker panel next to the bar.
03/14/2006 VIOL - BUILDING SVCS & SYSTEMS JVALENZU Violation · TFC 610 - A Type I hood shall be installed at or above all commercial cooking appliances that produce grease vapors and shall comply with the requirements of the International Mechanical Code. The kitchen equipment shall not be used until the hood system has been permitted and installed.
03/14/2006 VIOL - FIRE RESIST.RATED CONST JVALENZU Violation · TFC 703.1 - fire resistance rated construction shall be repaired. The drywall over the stage shall be repaired to cover the exposed ceiling members.
03/14/2006 VIOL - INT.FINISH, DEC. MATL'S JVALENZU Violation · TFC 805.1 - decorative materials suspended from ceilings shall be flame resistant in accordance with section 805.2 and NFPA 701 or be noncombustible. The decorations in the bar area shall be removed.
03/14/2006 VIOL - FIRE PROTECTION SYSTEMS JVALENZU Violation · TFC 901.6 - fire-extinguishing systems shall be maintained in an operative condition at all times and shall be repaired or replaced when defective. · Kitchen sprinkler system shall be inspected and maintained in accordance with NFPA standards · Portable fire extinguishers shall be inspected annually
03/14/2006 VIOL - FIRE PROTECTION SYSTEMS JVALENZU Violation · TFC 904.11.5 - portable extinguishers shall be provided within 30-feet of commercial-type cooking equipment and shall be a Class K rated extinguisher. In the kitchen.
03/14/2006 VIOL - FIRE PROTECTION SYSTEMS JVALENZU Violation · TFC 906.5, 906.6, 906.7 - portable fire extinguishers shall be located in a conspicuous place, shall not be obstructed or obscured from view, and shall be installed on the hangars or brackets supplied. There are extinguishers in the kitchen and the VIP room.
03/14/2006 VIOL - MEANS OF EGRESS JVALENZU Violation · TFC 1003.6 - the path of egress travel shall not be interrupted by any building component other than the means of egress component. Obstructions shall not be placed in the required width of a means of egress. There shall not be screen doors in front of exit doors; there shall be a clear path to all required exits including from the VIP room.
03/14/2006 VIOL - MEANS OF EGRESS JVALENZU Violation · TFC 1004.3 - every space or room used as an assembly occupancy shall have the occupant load posted in a conspicuous place.
03/14/2006 VIOL - MEANS OF EGRESS JVALENZU Violation · TFC 1008.1 - means of egress doors shall be readily distinguishable such that they are easily recognizable as doors; shall not be concealed by curtains, drapes, decorations, or similar materials. The decorations shall be removed from the door in the VIP room.
03/14/2006 VIOL - MEANS OF EGRESS JVALENZU Violation · TFC 1008.1.8.4 - manually operated flush bolts or surface bolts are not permitted. There are several doors that have them and shall be removed.
03/14/2006 VIOL - MEANS OF EGRESS JVALENZU Violation · TFC 1008.1.9 - each door in a means of egress from an occupancy of Group A having an occupant load of 100 or more shall have panic or fire exit hardware.
03/14/2006 VIOL - MEANS OF EGRESS JVALENZU Violation · TFC 1011.1 - exits and exit access doors shall be marked by an approved illuminated exit sign. A sign is required in the VIP room

Completed Inspections

Case Status: FIELD
Case Number: T06FR00362
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/23/2006 VIOL - COMPRESSED GASES JVALENZU Approved