Fire Inspection

Outstanding Inspections

Case Number: T06FR00339
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
03/13/2006 VIOL - BUILDING SVCS & SYSTEMS KFOSTER Correction Required TFC-605.1 Electrical Hazard. 4) Replace multi-plug adaptor with a UL/FM approved power strip with over current protection, for outlet by register.
03/13/2006 VIOL - FIRE PROTECTION SYSTEMS KFOSTER Correction Required TFC-901.6 Inspection, testing and maintenance. 2) Provide documention of last hood inspection, for heads over deep fyer.
03/13/2006 VIOL - FIRE PROTECTION SYSTEMS KFOSTER Correction Required TFC-904.11.6.3 Cleaning. 3) Clean sprinkler head by grill in kitchen area.
03/13/2006 VIOL - COMPRESSED GASES KFOSTER Correction Required TFC-3003.3.3 Compressed Gas Cylinders. 1) Chain compressed gas cylinders to prevent beig knocked over.