Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/10/2006

Applicant:

BYNUM GARY D & DENISE M TR

Description:

Full inspection done 3/10/06.

Outstanding Inspections

Case Number: T06FR00335
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
03/10/2006 INSP - FULL BCOBB Violation Please correct the following Tucson Fire Code violations listed below: Notes: C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it.
03/10/2006 VIOL - BUILDING SVCS & SYSTEMS BCOBB Violation Electric service panels: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. *** Clear area around electric service panels.
03/10/2006 VIOL - FIRE PROTECTION SYSTEMS BCOBB Violation Fire extinguishers: TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. *** Extinguishers shall have been tested and tagged within the last 12 months, and shall be mounted in an appropriate manner.
03/10/2006 VIOL - MEANS OF EGRESS BCOBB Violation Emergency lighting: TFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. *** Repair existing center emergency light.
03/10/2006 VIOL - MEANS OF EGRESS BCOBB Violation Exit sign visibility: TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. *** Remove boxes that block view of Exit sign by back door. Re-inspection scheduled for 3/28/06.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR00335
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/03/2006 COMPL - REINSPECTION BCOBB Approved All abated- [3/31/06] good job. No further action.