Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

03/03/2006

Applicant:

CITY OF TUCSON

Description:

AST - Tank Inspection

Outstanding Inspections

Case Number: T06FR00273
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
INSP - AST/UST None Not Inspected
03/03/2006 VIOL - FLAMMABLE LIQUIDS KFOSTER Correction Required TFC-3403 Electrical 1) Provide a copy of Electrical "Final" Inspection. TFC-3404.2.3 Label Signs 2) Label what's inside tanks & capacity. TFC-3404.2.7.3.4 Installation of venting piping. 3) Complete vent piping to exterior of building. TFC-3404.2.7.4 Emergency Venting. 4) Install secondary vent caps on AST's upstairs. TFC-3401.4 Permits 5) Obtain proper permits for installation of "Used Oil" AST Tank before installaion.