Full Inspection--SIP

Outstanding Inspections

Case Number: T06FR00241
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
VIOL - MEANS OF EGRESS None Not Inspected
02/28/2006 INSP - SELF INSPECTION PROGRAM JDAVIS Correction Required
02/28/2006 VIOL - ADMINISTRATION JDAVIS Correction Required TFC 102.3; 105.3.3 Obtain a C of O
02/28/2006 VIOL - PRECAUTION AGAINST FIRE JDAVIS Correction Required TFC 315.2.2 Do not store combustibles, including stock, in the required with of an exit
02/28/2006 VIOL - FIRE SERVICE FEATURES JDAVIS Correction Required TFC 1008.1.8 Main exit doors..."These doors to remain unlocked while the building is occupied
02/28/2006 VIOL - FIRE SERVICE FEATURES JDAVIS Correction Required TFC 505.1 Provide Premise ID
02/28/2006 VIOL - BUILDING SVCS & SYSTEMS JDAVIS Correction Required TFC 605.3 Electrical panels shall be clear of obstructions: 30 inches in width, 36 inches in front and 72 inches from the ground upward
02/28/2006 VIOL - FIRE PROTECTION SYSTEMS JDAVIS Correction Required TFC 901.1 Fire extinguisher shall not be obstructed or blocked