Case: T06FR00115
Case Details
Entered Date:
02/01/2006
Applicant:
OUR TOWN FAMILY CENTER INC
Description:
Group home checklist fire inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR00115
Case Description: INSPECTION
Total Completed Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 28. TFC 1025.1 General emergency escape and rescue. Is required in all sleeping areas. 1. cars parked next to east side of bedrooms must kept back 3' for emergency exiting for bedrooms |
| 02/01/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 26.TFC 1008.18 Door operation No double key dead-bolt locks, no special knowledge needed, no slide bolt locks. Only one unlatching device, Except group R’s can have night latch, indicating dead bolt, or security chain on exits only 1. Remove slide bolt lock on rear door |
| 02/01/2006 | VIOL - ADMINISTRATION | SHIGGINB | Approved | 12. TFC 102.3 Change of use of a building Must have it posted, must have correct occupancy type, and licensed amount must match occupancy class. R3 or R4 Date of C/O defines TFC used for regulation. 1. need to post CofO |
| 02/01/2006 | VIOL - FIRE SERVICE FEATURES | SHIGGINB | Approved | 1. TFC 2003 505.1 Addressing All building will have approved address numbers plainly legible & visible from the street fronting the property. Min. 3” high w/ contrasting background. 1. place address on building so to be seen from street |
| 02/01/2006 | INSP - FULL | SHIGGINB | Approved | DES group home inspection |