Description:

LIVEWIRES OUTSIDE AT UPROOTED LIGHTPOST, CLAIMS HAS BEEN SHOCKED, HOLES IN KITCHEN SINK. RODENT INFESTATION. HOLE IN CLOSET. LIVEWIRE AT SMOKE ALARM. LANDLORD TENANT ISSUES GOING TO COURT.

Outstanding Inspections

Case Number: T06DV01934
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
NPO - UNSECURED BUILD OR STRUC None Not Inspected
VIOL(EL) - CIRCUITS None Not Inspected
VIOL(EL)-SUBPANELS/DISCONNECTS None Not Inspected
NPO(EL)-WIRING/SWITCH/OUTLT/FX None Not Inspected
NPO(PL)-WATER HEATERS None Not Inspected
VIOL(SA) - BATHS None Not Inspected
VIOL(SA) - KITCHEN None Not Inspected
NPO - SMOKE ALARMS None Not Inspected
11/29/2006 INSP - INITIAL CODE ENFORCMENT RMENDOZA Violation WATER HEATER INSTALLED WITHOUT PERMIT. NO TEMPERATURE RELIEF DRAIN LINE. VENT PIPE INSTALLED INCORRECTLY AND NOT PROPERLY SEALED. CLOTHES DRYER DISCONNECT INSTALLED IN WATER HEATER CLOSET WITHOUT PERMIT. DRYER CONNECTION IS HANGING OUTSIDE OF BACK WALL AND NOT PROPERLY SECURED. UNITS LACKS SMOKE DETECTORS ELECTRICAL SERVICE OUTLET IN THE MAIN BEDROOM EAST WALL IS SEVERLY DAMAGED AND UNUSEABLE. CIRCUIT IS ALSO ENERGIZED. UNERGIZED CIRCUIT IN THE HALLEWAY IS EXPOSED AND NOT CAPPED. EXTENSION CORD IS BEING USED TO SUPPLY POWER TO WASHING MACHINE AND OUTLET IS TAPED TO THE DOORWAY FRAME. FRONT DOOR DOES NOT SEAL PROPERLY. DOOR FRAME IS CRACKED AND BROKEN. HOLE IN WALL NEAR FRONT DOOR. CLOSET DOOR NEAR KITCHEN AREA HAS A LARGE HOLE. INSIDE THE CLOSET AREA DRYWALL HAS BEEN REMOVED EXPOSING WALL FRAMING. KITCHEN SINK CABINET AND WALL HAS BEEN SEVERLY DAMAGED BY WATER AND IS UNUSEABLE. WALL AND WINDOW SILL ABOVE SINK SHOWS SIGNS OF WATER DAMANGE. SPLASH GAURD HAS SEPERATED FROM THE WALL. BATHROOM SINK CABINET IS DETERIORATED AND REQUIRES REPAIR

Completed Inspections

Case Status: COMPLIAN
Case Number: T06DV01934
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/28/2007 INSP - FOLLOW UP CODE ENFORCE RMENDOZA Approved ALL WORK COMPLETE EXCEPT PERMITS FOR WATER HEATER. CONTACTED OWNER - STATED PERMITS ARE BEING APPLIED FOR. FOLLOW-UP 4-09-07.

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T06DV01934
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 3
Date Name
11/29/2006 CONTACTED BY PHONE
12/18/2006 CONTACTED BY MAILING
06/21/2007 VIOLATION CLOSED