Case: T05FR01947
Case Details
Entered Date:
12/28/2005
Applicant:
MONTEREY WATER COMPANY
Description:
merchandise boxes all over the isles, boxes on the floor which you step on.
Outstanding Inspections
Case Number: T05FR01947
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/03/2006 | VIOL - PRECAUTION AGAINST FIRE | JDAVIS | Correction Required | 313.2.2 Do not block exits with stock on the sales floor and in the stock room. 315.1 combustible stock shall be orderly |
01/03/2006 | VIOL - BUILDING SVCS & SYSTEMS | JDAVIS | Correction Required | 605.3 Place blanks in the electrical panel where the breakers are missing 605.5 Do not use extension cords as a substitute for permanent wiring: Remove the cord above the baler. |
01/03/2006 | VIOL - FIRE RESIST.RATED CONST | JDAVIS | Correction Required | Fire resisitve construction shall be maintained. There is a broken ceiling tile in the stock room above the managers office door. |
01/03/2006 | VIOL - COMPRESSED GASES | JDAVIS | Correction Required | 3003.3 Compressed gas cylinders shall be secured from accidental dislodgement. A. In stock room B. On display floor next to the balloons |
12/28/2005 | INSP - FULL | RDUARTE | Approved | Dollar tree store, merchandise boxes on isles, boxes on floor which you step on, overcrowded store with merchandise. |