Case Number: T05FR01897
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2005 | INSP - FULL | EGRIFFIN | Violation | |
| 12/09/2005 | VIOL - FIRE PROTECTION SYSTEMS | EGRIFFIN | Violation | Currently you have a residential type cooking appliance in your kitchen, that is used once per month. Traditionally this does not require a hood automatic fire extinguishing system. Only commercial appliances require this system. But, this system still must be maintained under IFC 901.6, which states: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Removal of the system shall only be done with permission from The City of Tucson Fire Marshall Deputy Chief Dan Uthe 797 East Ajo Road Tucson, Arizona 85726-7210 Or the system must be restored. |