Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/08/2005

Applicant:

BAGGINS INC

Description:

Fire Inspection

Outstanding Inspections

Case Number: T05FR01890
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
VIOL - COMPRESSED GASES None Not Inspected
12/08/2005 VIOL - FIRE PROTECTION SYSTEMS KFOSTER Correction Required TFC-3003.3. Compressed Gase Cylinders/ Secure compressed gas cylinders to prevent being knocked over.
12/08/2005 VIOL - FIRE PROTECTION SYSTEMS KFOSTER Correction Required TFC-605.1 Electrical Hazards / Install spacer blanks inside electrical pannels (2 pannel boxes)
12/08/2005 VIOL - FIRE PROTECTION SYSTEMS KFOSTER Correction Required TFC-901.6 Inspection, Testing, Maintenance / Replace missing grates over grill. TFC-906.7 Portable Fire Extinghiushers / Mount fire extinguisher in a permant location in kitchen area.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01890
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/28/2005 VIOL - BUILDING SVCS & SYSTEMS KFOSTER Approved Approved.