Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/02/2005

Applicant:

KIM HUONG KWUN & CHONGHEE

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01873
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
12/02/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage
12/02/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Electrical hazard
12/02/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Working space
12/02/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3.1 Electrical room
12/02/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extinsion cord
12/02/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Fire alarm
12/02/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6.1 Sprinkler obstructions
12/02/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 907.2.10 Smoke detector
12/02/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit signs
12/02/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 Emergency illumination

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01873
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/16/2005 INSP - FULL TKNAPP Approved