Case: T05FR01869
Case Details
Entered Date:
12/02/2005
Applicant:
MIRASOL INC
Description:
Full Fire Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01869
Case Description: INSPECTION
Total Completed Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2005 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 26.TFC 2003 1008.18 Door operation No double key dead-bolt locks, no special knowledge needed, no slide bolt locks Remove or replace double-keyed dead bolt lock on the front door and the door to the pantry. |
| 12/02/2005 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | 23. TFC 2003 603.1 & 316.2 Fuel fired appliances and house cleaning. keep paper bags and any object that would block the air vent to the hot water heater. |
| 12/02/2005 | VIOL - FIRE RESIST.RATED CONST | SHIGGINB | Approved | 18. TFC 2003 703.1Must be repair w/ fire resistive materials Repair drywall in hot water room on west side of home |
| 12/02/2005 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | TFC 2003 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. The hot water room in the pantry must be sprinkler. |
| 12/02/2005 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | TFC 2003 901.6.2 Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. #15,16,17. Have all fire protection sys. test records on site. |
| 12/02/2005 | VIOL - ADMINISTRATION | SHIGGINB | Approved | TFC 102.3 2003 Change of use of a building Must have it posted, must have correct occupancy type, and licensed amount must match occupancy class. #12 Must have proper C of O posted |
| 12/02/2005 | VIOL - FIRE SERVICE FEATURES | SHIGGINB | Approved | TFC 2003 506.1 Security devices hindering access A knots box may be required if security devices block access #3,#4 Must provide TFD Access to gate openner on kleindale. KnoxBox may be requiered |
| 12/02/2005 | INSP - FULL | SHIGGINB | Approved | This is a BHL for 10, R4 sprinklered Check list used |