Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T05FR01859
Case Details
Entered Date:
11/28/2005
Applicant:
RIO SECO PREMIER LLC
Description:
complaint
Outstanding Inspections
Case Number: T05FR01859
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COMPL - INITIAL INSPECTION | None | Not Inspected |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01859
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2005 | VIOL - FIRE SERVICE FEATURES | EGRIFFIN | Approved | Currently there is a fire lane missing, southwest corner of property. A new fire lane shall to be posted at the Southwest corner. As per the following IFC requirements: Section D101 SIGNS Every fire apparatus access roadway required under the authority of this section shall be posted with signs installed at points not more than one-hundred (100) feet apart along the length of the required fire apparatus access roadway. The bottom of every such sign shall not be less than seven (7) feet or more than ten (10) feet from the ground surface level. Signs shall be posted to face the direction of travel. Construction, installation, and maintenance of the signs shall be done at no expense to the City. Materials and locations of each sign shall be indicated in the plans submitted to the fire department. Fire access signs shall conform to the Manual on Uniform Traffic Control Devices. The required sign shall be the international NO PARKING sign with a standard sign size (width and height) of 12 x 18 inches (300 x 450 mm), on a white reflective background. The international NO PARKING symbol shall be a black P, six inches high. Underneath the NO PARKING symbol, in one-and-five-eighths inch high and one-quarter inch stroke, in red lettering it shall read: FIRE ACCESS TOW AWAY |
| 12/21/2005 | COMPL - REINSPECTION | EGRIFFIN | Approved | 1). Currently there is a fire lane sign missing, southwest corner of property. A new fire lane shall to be posted at the Southwest corner. As per the following IFC requirements: Section D101 SIGNS Every fire apparatus access roadway required under the authority of this section shall be posted with signs installed at points not more than one-hundred (100) feet apart along the length of the required fire apparatus access roadway. The bottom of every such sign shall not be less than seven (7) feet or more than ten (10) feet from the ground surface level. Signs shall be posted to face the direction of travel. Construction, installation, and maintenance of the signs shall be done at no expense to the City. Materials and locations of each sign shall be indicated in the plans submitted to the fire department. Fire access signs shall conform to the Manual on Uniform Traffic Control Devices. The required sign shall be the international NO PARKING sign with a standard sign size (width and height) of 12 x 18 inches (300 x 450 mm), on a white reflective background. The international NO PARKING symbol shall be a black P, six inches high. Underneath the NO PARKING symbol, in one-and-five-eighths inch high and one-quarter inch stroke, in red lettering it shall read: FIRE ACCESS TOW AWAY |