Case: T05FR01851
Case Details
Entered Date:
11/23/2005
Applicant:
TANAGER COMPANY
Description:
on ground floor, caller states the painic hardware was removed and door has a metal bar across, so in case of a fire you would have to remove bar to get out, caller also states the front entrance is block with supplies from time to time
Outstanding Inspections
Case Number: T05FR01851
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2005 | INSP - FULL | ALOPEZ | Violation | caller states on ground floor, panic hardware was taken off of exit door and a bar was put in place of, so in case of fire you would have to remove the bar to exit, caller also states entrance blocked from time to time with supplies. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01851
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2005 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | tfc1008.1.8.3 You shall place a sign over the exit from pool area reading " THIS DOOR IS TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED " |
| 12/23/2005 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | tfc1027.6 Panic hardware on SE corner exit shall be the only locking devive on the door. |
| 12/23/2005 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | tfc 1026.5 Emergency lighting in pool area needs servicing or replacement of battery. |
| 12/23/2005 | VIOL - PRECAUTION AGAINST FIRE | DRAMIREZ | Approved | 315.2.3 Electrical room shall be free from storage. |
| 12/23/2005 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | tfc605.4 Multi-plugs shall not be used (i.e. Behind TV sets located on south wall ) |
| 12/23/2005 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | tfc605.5 Extension cords shall not be used for permanent wiring. 1) x-3 behind counter in retail shop 2) x-2 in boiler room |