Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

11/23/2005

Applicant:

TANAGER COMPANY

Description:

on ground floor, caller states the painic hardware was removed and door has a metal bar across, so in case of a fire you would have to remove bar to get out, caller also states the front entrance is block with supplies from time to time

Outstanding Inspections

Case Number: T05FR01851
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
11/23/2005 INSP - FULL ALOPEZ Violation caller states on ground floor, panic hardware was taken off of exit door and a bar was put in place of, so in case of fire you would have to remove the bar to exit, caller also states entrance blocked from time to time with supplies.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01851
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 6
End Date Description Inspector Results Comments
12/23/2005 VIOL - MEANS OF EGRESS DRAMIREZ Approved tfc1008.1.8.3 You shall place a sign over the exit from pool area reading " THIS DOOR IS TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED "
12/23/2005 VIOL - MEANS OF EGRESS DRAMIREZ Approved tfc1027.6 Panic hardware on SE corner exit shall be the only locking devive on the door.
12/23/2005 VIOL - MEANS OF EGRESS DRAMIREZ Approved tfc 1026.5 Emergency lighting in pool area needs servicing or replacement of battery.
12/23/2005 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved 315.2.3 Electrical room shall be free from storage.
12/23/2005 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved tfc605.4 Multi-plugs shall not be used (i.e. Behind TV sets located on south wall )
12/23/2005 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved tfc605.5 Extension cords shall not be used for permanent wiring. 1) x-3 behind counter in retail shop 2) x-2 in boiler room