Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

11/21/2005

Applicant:

SDR ASSOCIATES

Description:

please comply with the following tucson fire codes

Outstanding Inspections

Case Number: T05FR01835
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
11/21/2005 VIOL - PRECAUTION AGAINST FIRE BCOBB Correction Required TFC 315.2.1 Piled storage shall be kept 18 inches below sprinkler head.
11/21/2005 VIOL - BUILDING SVCS & SYSTEMS BCOBB Correction Required TFC 605.6 Open junction boxes and open wire splicing shall be prohibited; approved covers shall be provided.
11/21/2005 VIOL - MEANS OF EGRESS BCOBB Correction Required TFC 1011.1 Exits Shall be readily visible
11/21/2005 VIOL - MEANS OF EGRESS BCOBB Correction Required TFC 1026.5 Exits shall be lit, and have back up power.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01835
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/02/2005 INSP - REINSPECTION BCOBB Approved Re inspection very good; no violations; fire sprinkler and extinguisher records were produced and in order; C of O being looked into...Mngr believes it to be with corperate headquarters;