Case: T05FR01835
Case Details
Entered Date:
11/21/2005
Applicant:
SDR ASSOCIATES
Description:
please comply with the following tucson fire codes
Outstanding Inspections
Case Number: T05FR01835
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
11/21/2005 | VIOL - PRECAUTION AGAINST FIRE | BCOBB | Correction Required | TFC 315.2.1 Piled storage shall be kept 18 inches below sprinkler head. |
11/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Correction Required | TFC 605.6 Open junction boxes and open wire splicing shall be prohibited; approved covers shall be provided. |
11/21/2005 | VIOL - MEANS OF EGRESS | BCOBB | Correction Required | TFC 1011.1 Exits Shall be readily visible |
11/21/2005 | VIOL - MEANS OF EGRESS | BCOBB | Correction Required | TFC 1026.5 Exits shall be lit, and have back up power. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01835
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/02/2005 | INSP - REINSPECTION | BCOBB | Approved | Re inspection very good; no violations; fire sprinkler and extinguisher records were produced and in order; C of O being looked into...Mngr believes it to be with corperate headquarters; |