Case: T05FR01756
Case Details
Entered Date:
11/09/2005
Applicant:
H I M CORPORATION
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01756
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage in rear stockroom shall be maintained 2 feet below ceiling. |
| 11/09/2005 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 505.1 Address numbers shall be posted as per Pima County standards. |
| 11/09/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Electrical conduit located in the freezer shall be secured to the wall. |
| 11/09/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cord located at front counter shall not be used as permenant wiring. |
| 11/09/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 901.6 Portable fire extinguishers shall be inspected annually. |
| 11/09/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 The comercial cooking system shall be serviced bi-annually |
| 11/09/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 Extinguishers shall be mounted on hangers or brackets. |
| 11/09/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 The exit doors located in the kitchen area on the east and west side shall be readily openable from the egress side without the use of a key or special knowledge. |
| 11/09/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 The emergency illumination lights located at the lobby shall be repaired. |
| 11/09/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Exit hallway at east exit shall be maintained free from obstructions. |
| 11/09/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 Compressed gas cylinder at east exit shall be secured. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01756
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2006 | INSP - FULL | TKNAPP | Approved |