Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/07/2005

Applicant:

GLOVER ASSOCIATES LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01727
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
11/07/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 A working space of 36 inches deep and the width of the panels shall be maintained in front of electrical panels at south door.
11/07/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The junction boxes located in the boiler room shall have approved covers.
11/07/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 A sign shall be posted on the north door stating This door shall remain unlocked when building is occupied.
11/07/2005 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.4 Material Safety Data Sheets shall be readily availible on the premises.
11/07/2005 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5.1 Individual containers that contain hazardous materials shall be labeled.
11/07/2005 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 The commpressed gas cylinder located behind the dry cleaning maching shall be secured to prevent it from falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01727
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/22/2005 INSP - FULL TKNAPP Approved