Case: T05FR01727
Case Details
Entered Date:
11/07/2005
Applicant:
GLOVER ASSOCIATES LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01727
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 A working space of 36 inches deep and the width of the panels shall be maintained in front of electrical panels at south door. |
| 11/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The junction boxes located in the boiler room shall have approved covers. |
| 11/07/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 A sign shall be posted on the north door stating This door shall remain unlocked when building is occupied. |
| 11/07/2005 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.4 Material Safety Data Sheets shall be readily availible on the premises. |
| 11/07/2005 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.5.1 Individual containers that contain hazardous materials shall be labeled. |
| 11/07/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 The commpressed gas cylinder located behind the dry cleaning maching shall be secured to prevent it from falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01727
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2005 | INSP - FULL | TKNAPP | Approved |