Case: T05FR01720
Case Details
Entered Date:
11/04/2005
Applicant:
ASHLAND GROUP LLC 16.6564% & SWC
Description:
Full Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01720
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2005 | INSP - FULL | DRAMIREZ | Approved | TFC 1013.4.1 Must maintaine aisle with clearence in stockroom to rear of building.( West wall) |
11/09/2005 | VIOL - PRECAUTION AGAINST FIRE | DRAMIREZ | Approved | TFC315.2 Storage in N. stockroom shall be orderly. |
11/09/2005 | VIOL - HIGH PILED COMBUSTIBLES | DRAMIREZ | Approved | TFC2305.4 Aisles in main stockroom must maintained with 44 in. width. |
11/09/2005 | VIOL - HIGH PILED COMBUSTIBLES | DRAMIREZ | Approved | |
11/09/2005 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC605.1 Cover for water heater must be replaced. TFC605.3 Must maintain 36 in. working space in front of electrical braker panal located on north wall of main stockroom. TFC605.6 Light swich on N. wall next to exet in main stockroom must have an approved cover. |
11/09/2005 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | |
11/09/2005 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | TFC703.1 Missing cieling tiles through out building must be replaced. |
11/09/2005 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC901.1 Extinguisher in rear stockroom (west side) must be serviced. TFC901.6 Must maintain 36 in. of clearence around sprkler. riser. TFC901.6 Extinguisher in main stockroom must be serviced. TFC901.6.2 Shall present records of sprkler. syst. annual inspection test. |
11/09/2005 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | 1027.2 required exit located on SE corner must be free from obstruction and remained unlocked during business hrs. 2. Exit to NW shall not be obstructed. 1027.6 Exit door on SEcorner of bld have only one locking device on it (ie thumb turn lock 1013.4.1 must maintaine aisle with 28" clearence in stock room to rear of bld (WS) 1011.1 Exit sign for the NW exit shall be visable from sales floor. |