Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01719
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 20
End Date Description Inspector Results Comments
11/03/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 310.3 Two No Smoking signs shall be posted in the south and west storage areas.
11/03/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located above the office shall be maintained 2 feet below the level of the ceiling.
11/03/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located in the south storage room shall be maintained 2 feet below the level of the ceiling.
11/03/2005 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 504.2 The exterior door leading to the office shall have a sign affixed to the exterior side of the door with the words This Door Blocked.
11/03/2005 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 505.1 Address numbers in accordance with Pima County address display requirements shall be posted on the outside of the building.
11/03/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Blanks shall be installed in electrical panel at west wall where breakers are missing.
11/03/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 The electrical control panels located on the east wall of the sales room shall be accessible.
11/03/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4 The multiplug adapter attached to the extension cord at the east rollup door is prohibited and shall not be used.
11/03/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 The extinsion cord located in the restroom at the northeast corner of the south sales floor shall not be used as permanent wiring, and shall not be affixed to walls.
11/03/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 The extinsion cords located in the office shall not be used as a substitute for permanent wiring. Extension cords shall only be used for portable appliances.
11/03/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open junction box located above the restroom in the south sales room shall have an approved cover.
11/03/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open junction boxes located at the south east corner of the sales room shall have approved covers.
11/03/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open junction boxes located near the north exit from the sales room at the ceiling shall have an approved cover.
11/03/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 The exit doors from the sales floor area shall be marked by approved illuminated exit signs.
11/03/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1013.4 Aisles shall be maintained clear in the south and west storage areas.
11/03/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1014.2.1 Where two exits are required (sales floor area) exits shall be placed a distance apart equal to not less than one half of the length of the diagonal dimension of the area.
11/03/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1018.1 The sales floor area shall be provided with at least two exits.
11/03/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 Emergency illumination shall be provided for the sales floor area.
11/03/2005 VIOL - LUMBER YARD & WOOD FAC. TKNAPP Correction Required 1904.2 Three portable fire extinguishers rated at 4A shall be supplied for the south room. Extinguishers shall be mounted on hangers or brackets. 906.7
11/03/2005 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5.1 Containers located within the liquid storage cabinet shall have lables indicating their contents.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01719
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/22/2006 INSP - FULL TKNAPP Approved