Case: T05FR01719
Case Details
Entered Date:
11/03/2005
Applicant:
HUIE-WONG AUDREY
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01719
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 20
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 310.3 Two No Smoking signs shall be posted in the south and west storage areas. |
| 11/03/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located above the office shall be maintained 2 feet below the level of the ceiling. |
| 11/03/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located in the south storage room shall be maintained 2 feet below the level of the ceiling. |
| 11/03/2005 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 504.2 The exterior door leading to the office shall have a sign affixed to the exterior side of the door with the words This Door Blocked. |
| 11/03/2005 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 505.1 Address numbers in accordance with Pima County address display requirements shall be posted on the outside of the building. |
| 11/03/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Blanks shall be installed in electrical panel at west wall where breakers are missing. |
| 11/03/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 The electrical control panels located on the east wall of the sales room shall be accessible. |
| 11/03/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 The multiplug adapter attached to the extension cord at the east rollup door is prohibited and shall not be used. |
| 11/03/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 The extinsion cord located in the restroom at the northeast corner of the south sales floor shall not be used as permanent wiring, and shall not be affixed to walls. |
| 11/03/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 The extinsion cords located in the office shall not be used as a substitute for permanent wiring. Extension cords shall only be used for portable appliances. |
| 11/03/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box located above the restroom in the south sales room shall have an approved cover. |
| 11/03/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction boxes located at the south east corner of the sales room shall have approved covers. |
| 11/03/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction boxes located near the north exit from the sales room at the ceiling shall have an approved cover. |
| 11/03/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1011.1 The exit doors from the sales floor area shall be marked by approved illuminated exit signs. |
| 11/03/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4 Aisles shall be maintained clear in the south and west storage areas. |
| 11/03/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1014.2.1 Where two exits are required (sales floor area) exits shall be placed a distance apart equal to not less than one half of the length of the diagonal dimension of the area. |
| 11/03/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1018.1 The sales floor area shall be provided with at least two exits. |
| 11/03/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 Emergency illumination shall be provided for the sales floor area. |
| 11/03/2005 | VIOL - LUMBER YARD & WOOD FAC. | TKNAPP | Correction Required | 1904.2 Three portable fire extinguishers rated at 4A shall be supplied for the south room. Extinguishers shall be mounted on hangers or brackets. 906.7 |
| 11/03/2005 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.5.1 Containers located within the liquid storage cabinet shall have lables indicating their contents. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01719
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2006 | INSP - FULL | TKNAPP | Approved |