Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/03/2005

Applicant:

6942 E CALLE JUPITER LLC

Description:

Full Fire Inspection assisted living R4 checklist used

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01716
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
11/09/2005 VIOL - MEANS OF EGRESS SHIGGINB Approved TFC 2003 1008.18 Door operation No double key dead-bolt locks, no special knowledge needed, no slide bolt locks #26. Turn door knob around so lock is on the inside.
11/09/2005 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Approved TFC 2003 605.1 Abatement of electrical hazards Electrical wires in conduit, covers, and panels locked. # 6 1.Electrical wire on east side of home must be in conduit.
11/09/2005 INSP - FULL SHIGGINB Approved TFC 2003 605.5 Extension cords #20. Remove electrical cords between wall and closet door in southeast bedroom of N. hallway
11/09/2005 INSP - FULL SHIGGINB Approved TFC 2003 703.1Must be repair w/ fire resistive materials #18. 1. Repair wall behind heater in heater closet in N. hallway. 2. The vent in the ceiling must be connect to the roof vent with vent pipe. 3. Remove electrical cord from the vent. 4. Repair ceiling around vent.
11/09/2005 INSP - FULL SHIGGINB Approved This is an R4 assisted living home lic. 10. Has a C of O 7-27-99. is under the UFC 1994, No sprinklers required. checklist used