Description:

Full Fire inspection Asisted living R4

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01713
Case Description: INSPECTION
Total Completed Inspections - 7
End Date Description Inspector Results Comments
11/10/2005 VIOL - COMPRESSED GASES SHIGGINB Approved TFC 3004.1 O2 storage and Use Can be on a 45 degree, Must be secured w/ straps or rack No smoking signs must be posted on front door 1. Place " NO SMOKING " Sign on front door when O2 is stored or used in home.
11/10/2005 VIOL - MEANS OF EGRESS SHIGGINB Approved TFC 1008.18 Door operation No double key dead-bolt locks, no special knowledge needed, no slide bolt locks. 1. Remove double keyed dead bolt lock on front door with a thumb latch type lock
11/10/2005 VIOL - FIRE RESIST.RATED CONST SHIGGINB Approved TFC 703.1Must be repair w/ fire resistive materials #18 1. Repair ceiling above hot water heater in laundry room. 2. Repair wall in heater closet in west hallway
11/10/2005 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Approved TFC 603.1 & 316.2 Fuel fired appliances and house cleaning. #23 1. Cut vent in launtry door for better combustable air flow for hot water heater. 2. Cut vent in heater door for better combutable air flow for heater
11/10/2005 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Approved TFC 605.5 Extension cords #20 1. Remove extension cord in west bedroom
11/10/2005 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Approved TFC 605.1 Abatement of electrical hazards Electrical wires in conduit, covers, and panels locked. #6 1. All electrical wire on out side of home must be in conduit. 2. Door bell transformer must be scured ot wall
11/10/2005 INSP - FULL SHIGGINB Approved This is an R4 assisted Living home Lic. for 10 C of O 2/9/95 UFC 1994 Used, No sprinkler required. Check list used