Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/27/2005

Applicant:

SDR ASSOCIATES

Description:

FULL INSPECTION REPORT OF OCCUPANCY INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01696
Case Description: INSPECTION
Total Completed Inspections - 10
End Date Description Inspector Results Comments
10/27/2005 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved These two items abated. [10/20/05]
10/27/2005 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved TFC 315.2.2 Means of egress: Combustable material shall not be stored in exits or exit closures.
10/27/2005 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved TFC 315.2.1 Combustibles must be at least 18 inches below sprinkler heads.
10/27/2005 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved These two violations have been corrected. [as of 09/20/05]
10/27/2005 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved TFC 605.4 Multiplug adapters to have overcurrent protection.
10/27/2005 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved TFC 605.5 Extension cords not to be used as a substitute for permanent wiring. and [605.5.4] shall be grounded and in good condition.
12/02/2005 INSP - REINSPECTION BCOBB Approved All violations corrected; reinspection approved;
12/02/2005 VIOL - FIRE RESIST.RATED CONST BCOBB Approved no violations upon 12/02/05 reinspection
12/02/2005 VIOL - MEANS OF EGRESS BCOBB Approved
12/02/2005 INSP - FULL BCOBB Approved