Case Number: T05FR01692
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 18
End Date Description Inspector Results Comments
10/26/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located at the upstairs area of the stockroom shall be maintained 18 inches below the level of the sprinkler heads.
10/26/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located in the upstairs area in the stockroom shall not be located in the roof trusses.
10/26/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located on the east wall of garden center shall be maintained 18 inches below the level of the sprinkler heads.
10/26/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located on the ground floor of the south side stockroom area shall be maintained 18 inches below the level of the sprinkler heads.
10/26/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4 The multiplug adapter located by the sink at the fish tank area shall not be used.
10/26/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 The extension cord located at the front of the store at the main exit shall not be used as permanent wiring.
10/26/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 The extension cord located at the south exit from the garden area shall not be used as permanent wiring.
10/26/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 The extension cord located in the furniture area on the northside of the store shall not be used as permanent wiring.
10/26/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open junction box located at the ceiling fan area shall have an approved cover.
10/26/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open junction box located at the center of garden area at the celing shall have an approved cover.
10/26/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open junction box located at the north east exit door shall have an approved cover.
10/26/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open junction box located at the top of the stairs in the stockroom shall have an approved cover.
10/26/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1013.4.1 Aisles located at the ground level area on the south side of the stockroom shall be maintained clear and at least 28 inches wide.
10/26/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 2305.4 Aisles located at the north side of stockroom shall be kept clear of storage . During stocking operations aisles shall be unobstructed to a width of 44 inches.
10/26/2005 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5.1 All containers located in the small storage building at the northeast corner of the building shall be conspicuously marked or labeled.
10/26/2005 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 The compressed gas "CO2" cylinders located at the snack bar area shall be secured to keep them from falling
10/26/2005 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 The compressed gas "CO2" cylinders located by the trash compactor shall be secured to keep them from falling
10/26/2005 VIOL - FLAMMABLE LIQUIDS TKNAPP Correction Required 3404.3.4.4 Flammable and combustible liquids located in the small storage shed at the north east corner in excess of 10 gallons shall be removed or stored in a liquid storage cabinet.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01692
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/09/2005 INSP - FULL TKNAPP Approved