Case: T05FR01692
Case Details
Entered Date:
10/26/2005
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01692
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 18
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located at the upstairs area of the stockroom shall be maintained 18 inches below the level of the sprinkler heads. |
10/26/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located in the upstairs area in the stockroom shall not be located in the roof trusses. |
10/26/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located on the east wall of garden center shall be maintained 18 inches below the level of the sprinkler heads. |
10/26/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located on the ground floor of the south side stockroom area shall be maintained 18 inches below the level of the sprinkler heads. |
10/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 The multiplug adapter located by the sink at the fish tank area shall not be used. |
10/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 The extension cord located at the front of the store at the main exit shall not be used as permanent wiring. |
10/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 The extension cord located at the south exit from the garden area shall not be used as permanent wiring. |
10/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 The extension cord located in the furniture area on the northside of the store shall not be used as permanent wiring. |
10/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box located at the ceiling fan area shall have an approved cover. |
10/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box located at the center of garden area at the celing shall have an approved cover. |
10/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box located at the north east exit door shall have an approved cover. |
10/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box located at the top of the stairs in the stockroom shall have an approved cover. |
10/26/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4.1 Aisles located at the ground level area on the south side of the stockroom shall be maintained clear and at least 28 inches wide. |
10/26/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 2305.4 Aisles located at the north side of stockroom shall be kept clear of storage . During stocking operations aisles shall be unobstructed to a width of 44 inches. |
10/26/2005 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.5.1 All containers located in the small storage building at the northeast corner of the building shall be conspicuously marked or labeled. |
10/26/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 The compressed gas "CO2" cylinders located at the snack bar area shall be secured to keep them from falling |
10/26/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 The compressed gas "CO2" cylinders located by the trash compactor shall be secured to keep them from falling |
10/26/2005 | VIOL - FLAMMABLE LIQUIDS | TKNAPP | Correction Required | 3404.3.4.4 Flammable and combustible liquids located in the small storage shed at the north east corner in excess of 10 gallons shall be removed or stored in a liquid storage cabinet. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01692
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/09/2005 | INSP - FULL | TKNAPP | Approved |