Case: T05FR01661
Case Details
Entered Date:
10/18/2005
Applicant:
JUMBO PROPERTY GROUP LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01661
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage in the stockroom shall be orderly. |
| 10/18/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage in the stokroom shall be 18 inches below the level of the sprinkler heads. |
| 10/18/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.2 The area under the stairway shall not be used for storage. |
| 10/18/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.2 The electrical equipment room shall be free from storage. |
| 10/18/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 The storage in front of electrical panels in stockroom shall be 3 feet away from panels |
| 10/18/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3.1 A sign shall be posted on the electrical room door stating electrical room |
| 10/18/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cord extending through the wall to store to the west shall be removed. |
| 10/18/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The vent located in the janitors closet shall be replaced to fill hole in ceiling. |
| 10/18/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.6 The extinguisher at the top of the stairs in the stockroom.shall not be obstructed. |
| 10/18/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4.1 Aisles in the stokroom shall be maintained 28 inches wide. |
| 10/18/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Storage at the bottom of the stairs in the stockroom shall be removed. |
| 10/18/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Storage located at the north exit from the stockroom shall not block egress. |
| 10/18/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The flower display located at the west main exit shall not block exit |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01661
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2005 | INSP - FULL | TKNAPP | Approved |