Inspection

Outstanding Inspections

Case Number: T05FR01631
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 19
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
10/13/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy.
10/13/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage shall be maintained 2 feet below ceiling. (office)
10/13/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Electrical hazards shall be abated. The plug to the welder shall be repaired.
10/13/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of 30" width, 36" depth and 78" height shallbe provided in front of electrical service equipment. 1. S shop wall 2. N shop wall
10/13/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. 1. front office x 2 2. back office 3. shop area (W wall)
10/13/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC Multiplug adapters shall be prohibited. (W shop wall)
10/13/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually. (several throughout)
10/13/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (several throughout)
10/13/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Exit doors and pathways shall not be interrupted.
10/13/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8.3- Locks and latches shall be permitted proviede the following exists: 1. The lock is readily distinguishable as locked 2. A visible durable sign posted on the egress side stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED".
10/13/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted. 1. W office door 2. W shop door 3. S shop door
10/13/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.2- Exit signs shall be internally or externally illuminated.
10/13/2005 VIOL - WELDING & OTHER HOT WRK JLANGEJA Violation TFC 2606.4- The disconnect for welding operations shall be marked "EMERGENCY DISCONNECT" and shall be visible from the equipment.
10/13/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.1.1(1)- The maximum allowable quantity for class 1-B flammable liquids is 60 gallons. This quantity can be increased 100% if stored in an approved metal cabinet.
10/13/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.5.1- Individual containers shall be conspicuously marked or labeled in an approved manner. 1. motor oil tank 2. waste oil tank
10/13/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Compressed gas cylinders shall be secured.
10/13/2005 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3404.3.2.1.3- Storage cabinet doors shall be self-closing.
10/13/2005 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3405.3.6.2.7- Machines (solvent) shall be installed in accordance with their listing 1. shall be plugged into a GFCI 2. shall be located a minimum of 5 feet from unclassified electrical 3. shall have a fusible link on self-closing lid