Case: T05FR01631
Case Details
Entered Date:
10/13/2005
Applicant:
1331 PARTNERSHIP
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01631
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 19
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 10/13/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy. |
| 10/13/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage shall be maintained 2 feet below ceiling. (office) |
| 10/13/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Electrical hazards shall be abated. The plug to the welder shall be repaired. |
| 10/13/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of 30" width, 36" depth and 78" height shallbe provided in front of electrical service equipment. 1. S shop wall 2. N shop wall |
| 10/13/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. 1. front office x 2 2. back office 3. shop area (W wall) |
| 10/13/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC Multiplug adapters shall be prohibited. (W shop wall) |
| 10/13/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. (several throughout) |
| 10/13/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (several throughout) |
| 10/13/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- Exit doors and pathways shall not be interrupted. |
| 10/13/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8.3- Locks and latches shall be permitted proviede the following exists: 1. The lock is readily distinguishable as locked 2. A visible durable sign posted on the egress side stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". |
| 10/13/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted. 1. W office door 2. W shop door 3. S shop door |
| 10/13/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.2- Exit signs shall be internally or externally illuminated. |
| 10/13/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Violation | TFC 2606.4- The disconnect for welding operations shall be marked "EMERGENCY DISCONNECT" and shall be visible from the equipment. |
| 10/13/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.1.1(1)- The maximum allowable quantity for class 1-B flammable liquids is 60 gallons. This quantity can be increased 100% if stored in an approved metal cabinet. |
| 10/13/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.5.1- Individual containers shall be conspicuously marked or labeled in an approved manner. 1. motor oil tank 2. waste oil tank |
| 10/13/2005 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured. |
| 10/13/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3404.3.2.1.3- Storage cabinet doors shall be self-closing. |
| 10/13/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3405.3.6.2.7- Machines (solvent) shall be installed in accordance with their listing 1. shall be plugged into a GFCI 2. shall be located a minimum of 5 feet from unclassified electrical 3. shall have a fusible link on self-closing lid |