Case: T05FR01610
Case Details
Entered Date:
10/12/2005
Applicant:
1440 FACTORY LLC
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01610
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2005 | VIOL - ADMINISTRATION | TKNAPP | Correction Required | 104.7.2 To deturmine the acceptability of the spraying process, the owner shall provide a report prepaired by a qualified engineer or spray booth manufactures representative indicating that the spray booths are operating correctly. The report shall also indicate what areas are considered to be Class 1, Division 1 or Class 2, Division 1 hazardous locations in accordance with the ICC Electrical Code. |
| 10/12/2005 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.1.1 If spray booths are not operating correctly, spraying shall be discontinued untill indicated repairs are complete. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01610
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2005 | INSP - FULL | TKNAPP | Approved |