Case: T05FR01588
Case Details
Entered Date:
10/11/2005
Applicant:
HOLY FAMILY CENTER INC
Description:
full fire inspection
Outstanding Inspections
Case Number: T05FR01588
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2005 | INSP - FULL | RDUARTE | Correction Required |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01588
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2005 | VIOL - FIRE RESIST.RATED CONST | RDAVIS | Approved | TFC 703.1- repair holes in ceilings in #118 of nursing side at soiled utility rm. By 112 around electrical box cover for light in shower room next to 103, at floor board next to housekeeping. |
| 10/11/2005 | VIOL - FIRE PROTECTION SYSTEMS | RDAVIS | Approved | tfc 901.6 1. THE SPRINKLER and alarm systems shall have an annual test and insp and the results provided to me upon re inspection. 2. Replace escutcheon on sprinkler in lobby of hospice outside #18, by #110 , in mechanical room of ICU. |