Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/07/2005

Applicant:

SARIKAS JOHN MICHAEL TR & MERRIMAN VALLA

Description:

full inspection

Outstanding Inspections

Case Number: T05FR01580
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
INSP - LIFE SAFETY None Not Inspected
INSP - SPECIAL EVENT None Not Inspected
INSP - AST/UST None Not Inspected
10/07/2005 INSP - FULL FCONTRER Correction Required 2003 TFC-1008.1.8.3 Front exit door needs sign stating: This door to remain unlocked when building is occupied. 2003 TFC-605.3 Electrical J- box in the office missing cover plate. Make sure all extension cords are replaced with power surge protectors. 2003 TFC-904.11.5 Class K-rated fire extinguisher is missing the service tag,will need to have it serviced with tag attached. Extinguihers shall be service annually. The hood system was serviced.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01580
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/25/2005 INSP - NIGHT FCONTRER Approved final on this date 10/25/05.
10/25/2005 INSP - NIGHT FCONTRER Approved 2003 TFC-1008.1.8.3 Front exit door sign stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. 2003 TFC-605.3 Electrical junction box in office missing cover plate. 2003 TFC-904.11.5 Class-K rated portable extinguisher needs to be serviced.