Case: T05FR01567
Case Details
Entered Date:
10/05/2005
Applicant:
MAVERICK KING OF CLUBS INC (THE)
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01567
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 Multiplug adapter shall not be used at south bar. |
| 10/05/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords at south lamps or large boot sign shall not be used |
| 10/05/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The junction box located in the electrical room shall have an approved cover. |
| 10/05/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tiles in the kitchen shall be replaced. |
| 10/05/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Protective caps shall be provided for FDC |
| 10/05/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11 The nozzels for the comercial cooking system shall point at the cooking equipment. |
| 10/05/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit signs located in the kitchen at the south exit shall be repaired. |
| 10/05/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.6 The panic hardware at the south end of the kitchen exit shall be the only locking device on the door. |
| 10/05/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 The compressed gas cylinders at the south end of the kitchen shall be secured. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01567
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2005 | INSP - FULL | TKNAPP | Approved |