Case Number: T05FR01463
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 304.2 Combustible waste shall not be stored in basement. |
| 09/19/2005 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 505.1 Address numbers shall be posted as per Pima County standards. |
| 09/19/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Fluorescent light fixture at NE service bay shall have an approved cover. |
| 09/19/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 A working space shall be provided in front of electrical panels at north end of service bays. |
| 09/19/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Junction box at west side of basement for compressor shall have approved cover. |
| 09/19/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Junction box in basement at north wall shall have a approved cover. |
| 09/19/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | The stairway doors on the east and west side shall have their automatic closers repaired. Doors shall be allowed to close automatically. |
| 09/19/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Portable fire extinguisher at west stairs shall be inspected annually. Needs to be charged. |
| 09/19/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 Portable fire extinguisher at south service bay shall be hung on hanger. |
| 09/19/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 Portable fire extinguisher at SW service bay shall be hung on a hanger. |
| 09/19/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 The locking device on the SW and NE exits (steel bar) shall be removed. |
| 09/19/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4 Ailes in basement shall be free of obstructions. |
| 09/19/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Tires shall not obstruct west stairway. |
| 09/19/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 Compressed gas cylinder shall be secured to prevent from falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01463
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2005 | INSP - FULL | TKNAPP | Approved |