Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/19/2005

Applicant:

ALPHA PI OF ALPHA GAMMA RHO

Description:

inspection

Outstanding Inspections

Case Number: T05FR01461
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
09/19/2005 INSP - FULL EGRIFFIN Violation 1). Smoke detectors shall be tested and smoke detector log shall be submitted to TFD. IFC 901.6 2). All ceiling opening shall be repaired with approved materials. IFC 703.1 3). 6-month service due on kitchen hood extinguishing system IFC 904.11.6.3 4). Mount portable fire extinguisher in kitchen. IFC 904.11.5
09/19/2005 INSP - REINSPECTION EGRIFFIN Violation 1). Smoke detectors shall be tested and smoke detector log shall be submitted to TFD. IFC 901.6 2). All ceiling opening shall be repaired with approved materials. IFC 703.1 3). 6-month service due on kitchen hood extinguishing system IFC 904.11.6.3 4). Mount portable fire extinguisher in kitchen. IFC 904.11.5
10/18/2005 COMPLIANCE EGRIFFIN Violation all ok