Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

09/16/2005

Applicant:

TOYS R US INC

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01441
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
09/16/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 The electrical transformer located in the mezzanine shall be free from combustibles.
09/16/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.3 The ladder shall not be stored in the electrical equipment room.
09/16/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Blanks shall be used to fill the spaces left by missing breakers in the electrical panels in the computer room.
09/16/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 The electrical shutoff junction box for the bailer shall be secured.
09/16/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open junction boxes located at the far east end of the mezzanine and in the electrical room shall have an approved cover.
09/16/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing ceiling tiles located in the north side maintenance room and in the computer room shall be replaced.
09/16/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 The exit sign located at the southwest exit shall not be obstructed with paper.
09/16/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit signs located throughout the building shall be illuminated at all times.
09/16/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The southwest stockroom exit shall be maintained free from obstructions.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01441
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/04/2005 INSP - FULL TKNAPP Approved