Case: T05FR01430
Case Details
Entered Date:
09/16/2005
Applicant:
DOWNTOWN TUCSON STORAGE LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01430
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2005 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 506.1 A key box shall be provided to allow for FD access. |
| 09/16/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.4 The fire protection system shall be extended or augmented as necessary to maintain coverage below the loft areas throughout the building. |
| 09/16/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 903.3.3 Sprinkler coverage shall be provided under "tile roof" area located in space "D". |
| 09/16/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 912.2.2 Sign shall be provided for sprinkler connections on north side. |
| 09/16/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 Commpressed gas cylinders shall be secured. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01430
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2005 | INSP - FULL | TKNAPP | Approved |