Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

09/02/2005

Applicant:

THREE B S INVESTMENTS LLC

Description:

full inspection

Outstanding Inspections

Case Number: T05FR01380
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
09/02/2005 INSP - FULL FCONTRER Correction Required 2003 TFC-605.6 Open junction box shall be prohibited. next to noth exit door. 2003 TFC-904.11.2 Fire extingishers shall be service annually and shall have a current service tag. 2003 TFC-904.11.3 Hoods systems shall be cleaned at intervials to prevent accumlation grease. 2003 TFC-605.5 Extension cords shall not be use as permanent wiring. Replace with power surge protector. 2003 TFC-904.11.5 Automatic fire extinguishers system of commercial cooking shall be serviced at least every 6 months.