Case: T05FR01380
Case Details
Entered Date:
09/02/2005
Applicant:
THREE B S INVESTMENTS LLC
Description:
full inspection
Outstanding Inspections
Case Number: T05FR01380
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2005 | INSP - FULL | FCONTRER | Correction Required | 2003 TFC-605.6 Open junction box shall be prohibited. next to noth exit door. 2003 TFC-904.11.2 Fire extingishers shall be service annually and shall have a current service tag. 2003 TFC-904.11.3 Hoods systems shall be cleaned at intervials to prevent accumlation grease. 2003 TFC-605.5 Extension cords shall not be use as permanent wiring. Replace with power surge protector. 2003 TFC-904.11.5 Automatic fire extinguishers system of commercial cooking shall be serviced at least every 6 months. |