Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/31/2005

Applicant:

OTTIMO 22ND GROUP LLC (THE)

Description:

Inspection

Outstanding Inspections

Case Number: T05FR01361
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
08/30/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy.
08/30/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage of combustibles shall be maintained a minimum of 18" below sprinkler head deflectors. (supply room)
08/30/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.2- Combustible materials shall not be stored in exits or exit enclosures. 1. North exit from break room 2. Hallway connecting NE to NW exit enclosures.
08/30/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of not less than 30" width, 36" depth and 78" height shall be provided in front of electrical service equipment. (janitor's closet)
08/30/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually.
08/30/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire sprinkler system shall be serviced annually. *last sprinkler inspection was January 2004*
08/30/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be mounted on hangers or brackets. A break-glass type cabinet would also be acceptable. (front lobby)
08/30/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- The path of egress travel along a means of egress shall not be interrupted. 1. Conference room- need to maintain 3 feet around tables. 2. North exit corridors- files and cabinets impeding exit pathway