Case: T05FR01307
Case Details
Entered Date:
08/22/2005
Applicant:
D RAGEL ENTERPRISES LLC
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01307
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
08/17/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy. |
08/17/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 105.6.17- An operational permit is required to store, use or handle Class III-B liquids in excess of 60 gallons outside a building. |
08/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters shall be prohibited. (East wall) |
08/17/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. |
08/17/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. |
08/17/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- The path of egress travel shall not be interrupted. Desk is blocking exit path from office area. |
08/17/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1006.3- Emergency lighting shall be provided in the event of a power failure. They shall automatically illuminate exit access corridors, passageways and aisles. |
08/17/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1026.6- Guards shall be provided and shall form a protective barrier of not less than 42" high. (loft area) |
08/17/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Violation | TFC 2606.4- Aswitch or circuit breaker shall be provided so that welders and control equipment can be disconnected from the supply circuit. The disconnect shall be installed in accordance with the ICC Electrical Code. It shall be marked "EMERGENCY DISCONNECT" and shall be visible from the equipment. |
08/17/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.5.1- Individual containers shalol be conspicuously marked or labeled in an approved manner. ("WASTE OIL or USED OIL") |
08/17/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3403.1.3- Classified electrical equipment shall be required for solvent tank within 5 feet. |