Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/16/2005

Applicant:

DND NEFFSON CO

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01283
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
08/16/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 Clearance shall be maintained around the transformer in the stockroom
08/16/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in the stockroom shall be maintained 18 inches below the sprinkler heads
08/16/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 The electrical panels shall be accessable
08/16/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit signs in the stockroom shall be repaired

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01283
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/21/2005 INSP - FULL TKNAPP Approved