Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/16/2005

Applicant:

DND NEFFSON CO

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01282
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
08/16/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in stockroom shall be 18 inches below the sprinkler heads
08/16/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The stockroom doors shall not be blocked open
08/16/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit signs in the stockroom shall be repaired

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01282
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/07/2005 INSP - FULL TKNAPP Approved