Case: T05FR01251
Case Details
Entered Date:
08/11/2005
Applicant:
J & C SERVICE INC
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01251
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 08/10/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage of combustibles shall be maintained a minimum of 2 feet from the ceiling. |
| 08/10/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. |
| 08/10/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters shall be prohibited. Remove multiplug from N wall. |
| 08/10/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Fire resistive-rated construction shall be maintained. Replace missing ceiling tile. |
| 08/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. (x 2) |
| 08/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (x 2) |
| 08/10/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- The path of egress shall not be interrupted. Remove all items from pathways to exits. |
| 08/10/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1006.3- Emergency lighting shall be operational. (x 3) |
| 08/10/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.2- Exit signs shall be internally or externally illuminated. (x 2) |
| 08/10/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.7.1- Smoking shall be prohibited within 25 feet of storage, dispensing and open-use areas. Ash tray shall be moved 25 feet from near dispensing nozzle after extended. No smoking signs shall be provided in conspicuous locations and be plainly legible. 1. at entrance of store outside 2. West wall outside Signs shall state "NO SMOKING WITHIN 25 FEET" |